Working environment: -10~120°C, <95%RH, non cond.
Set point range: 40~120°C
Accuracy: typical ±4°C (calibrated points 4~5°C, others 7~8°C)
Switch type: automatic reset type: SPDT, 3 screw terminals
manual reset type: SPST, 2 screw terminals
Dead band: automatic reset type: typical 2~5°C
manual reset type: typical 5~15°C
Electrical connection: screw terminal, 1.5mm² wire, PG9
Electrical rate: AC1500V/1min
Insulation: ≥100MΩ in normal status, ≥10MΩ in moisture status
Contact: 250VAC/5A (Inductive load 4A), life≥105 times
Sensing element: stainless steel capillary and temperature sensing bulb with diameter Φ6mm, length 75~80mm, total length 700mm
Housing: fire retardant PC (UL94V-0)
Probe: TCH-2: 200mm stainless steel;
TCH-4:100mm stainless steel well
Protection: IP54(Automatic reset), IP43(Manual reset)
Weight: TCH-1: 270g; TCH-2: 330g; TCH-4: 360g
Approval: CE