Ultrasonic meter to measure flow and energy in a heat or cooling circuit with water using the ultrasonic principle. Important features are:
Non-wearing due to non-moving parts
Measuring range of flow 1:100 according to EN 1434, 1:1000 total range
Any mounting orientation, in flow or return, no setting sections or flow straighteners
Power measurement with maximum values, tariffs selectable
Data logger for system monitoring
60 monthly values Logbook
Battery or mains operated
Optical interface according to EN 62056-21
Wide range of communication modules for remote readout and system connection
2 slots for using 2 communication modules simultaneously
Also operable as a flow meter, cooling or combined heat/cooling meter
Self-diagnostics
The ultrasonic meters are used in residential or commercial buildings to acquire the amount of heat or heat/cooling energy consumed.
Technical details:
– Measurement accuracy: MID class 2 , EN 1434
– NRF-Number: 8533231
– Standard: EN 1434
– Temperature response threshold: Heat: 0.2 K , Cold: 0.2 K
– Sensing element, temperature: Pt500
– Cable length, sensor: 5 m
– DN: 50
– Mounting location: Meter: Return
– Dimensions (W x H x D): 143 x 42 x 136 mm
– Packaging unit: 1 pce
– Warranty: 24 Months