The Johnson Controls CD7000W0 is a CO2 transmitter designed for monitoring ambient carbon dioxide levels in commercial buildings, hospitals, and other HVAC environments. Here are some key details about it:
- Measurement Range: 0-2000 ppm
- Installation Mode: Wall Mount
- Accuracy: ± (50 ppm + 5% of reading)
- Output: 0-10V/4-20mA
- Warm-up Time: <180 seconds
- Power: 24VAC/DC ±10%
- Working Environment: -10°C to 50°C, 0-95% RH (no condensation)
- Storage Environment: -20°C to 70°C, 0-95% RH (no condensation)
The CD7000W0 helps improve air quality and operational efficiency by monitoring CO2 levels.